Technical Specifications

Specifications :
Typical office unit areas : 150sqm to 1,412sqm
Floor loading in office areas : 5kN/sqm
Ceiling height in office areas : 2.70 m

MATV and Telecommunication

: Cables for MATV and telephone provided from riser to junction board outside each unit. Horizontal cable trays are provided at corridors for additional MATV cables and telephone cables.
Escalators/Lifts :
- 2 sets of escalators serving levels one, two, and three.
- 6 lifts serving high-rise zone.
- 6 lifts serving mid-rise zone.
- 3 lifts serving low-rise zone.
- 3 carpark lifts.
- 1 fireman's lift.
- 2 goods/services lift.
External Finishes : Homogenous mix of granite stone cladding and aluminium curtain wall.
Internal Finishes : Granite stone on floor and walls at Public areas of Podium and at lift lobby of Tower Block.
Podium Business Floors : Walls (plaster & painted finish); Ceiling (600mm x 600mm acoustic ceiling on semi-concealed T-grid suspension system); and floor (mix of granite stone, homogeneous tiles & carpet on raised floor).

Carparking & Loading/unloading

:
- 348 covered car park lots.
- automatic carparking system.
- automatic payment machines at carpark lift lobbies.
- 2 lorry parks and 1 dock-leveller for loading and unloading on ground level.
Tower Business Floors : Walls (plaster & painted finish); Ceiling (600mm x 600mm acoustic ceiling on semi-concealed T-grid suspension system); and floor (raised floor).
Air-conditioning system : An air purging system (APS) expels stagnant air in the building every morning. All premises have variable air volume (VAV) boxes so that occupants can control room temperature.
Main Entrance Porch : 12.0m high aluminium framed curtain wall with two circular auto sliding doors on level one; and laminated glass skylite over atrium space of the Podium.
Electricity Supply :
- 400 Volts 3 Phase 50 Hz.
- Power allocation 100VA/sqm.
- 3 Standby 1500KVA diesel generators.

 